5
Categories and Use of Basic Application Instructions
DVP-PM Operation Instruction
5-68
Y0
ANS
T0
K100
S912
X2
X4
ANRP
M1000
M1049
Y1
ANS
T1
K200
S920
X3
X0
Y0
X2
M1048
Y2
Y0
X1
Y1
X3
Y1
1.
M1048 and D1049 are valid only when M1049 = ON.
2.
When Y0 = ON for more than 10 sec and the product fails to reach the front position X2, S912 = ON
3.
When Y1 = ON for more than 10 sec and the product fails to reach the back position X3, S920= ON.
4.
When backward switch X1 = ON and backward device Y1 = ON, Y1 will go OFF only when the product reaches
the back position switch X3.
5.
Y2 is ON when any alarm is enabled.
6.
Whenever X4 is ON, 1 active alarm will be reset. If there are several active alarms, the reset will start from the
alarm with the lowest number and then the alarm with second lower number, etc.