5 - 3 5
5
Installation and Wiring
WARNING:
1. Before performing battery/ battery cabinet installation, wiring and
UHSODFHPHQWSOHDVHWXUQRႇHDFKH[WHUQDOEDWWHU\FDELQHW¶VEUHDNHU4WR
completely disconnect the battery power from the UPS.
2. A battery can present a risk of electric shock and high short-circuit current.
Servicing of batteries and battery cabinets must be performed or supervised
E\TXDOL¿HGVHUYLFHSHUVRQQHONQRZOHGJHDEOHLQEDWWHULHVEDWWHU\FDELQHWV
and the required precautions. Keep unauthorized personnel away from
batteries and battery cabinets.
y
External Battery Cabinet Alarm
When any external battery cabinet connected to the UPS has the following problems,
the UPS system will sound an alarm. Please see the table below.
No.
External Battery Cabinet Status
Alarm
1
Battery Abnormal - Reversed
Sounds for 0.5 second every second.
2
Battery Ground Fault
Sounds for 0.5 second every second.
3
Battery Over Temperature
Sounds for 0.5 second every second.
4
Battery Under Temperature
Sounds for 0.5 second every second.
5
%DWWHU\%UHDNHU2ႇ
Sounds for 0.5 second every 3
seconds.
6
Battery Disconnected (Missing)
Sounds once every second.
7
Battery Over Charged
Long beep.
8
Battery Test Fail
Sounds for 0.5 second every second.
9
Battery End of Discharge Imminent
Sounds for 0.5 second every second.
10
Battery End of Discharge
Long beep.
11
Battery Life Time Expired
Sounds for 0.5 second every 3
seconds.
Содержание DPH-300K
Страница 8: ......
Страница 14: ......
Страница 60: ......
Страница 76: ......
Страница 227: ...8 1 8 Optional Accessories 8 Optional Accessories ...
Страница 230: ......
Страница 231: ...9 1 9 Maintenance Maintenance ...
Страница 233: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1 A1 ...
Страница 236: ......
Страница 237: ...A2 1 Appendix 2 Warranty Warranty A2 A2 ...
Страница 240: ... ...