6 - 2 2
Modulon DPH Series
6.2.6 Frequency Conversion Mode Start-up Procedures
WARNING:
1. Frequency Conversion mode is only applicable to single UPS but not to parallel
UPSs.
2. When the UPS runs in Frequency Conversion mode, once the inverter
EHFRPHVRႇWKHUHLVQRE\SDVVSRZHUVXSSO\LQJWRWKHORDGV
1
Ensure that the Manual Bypass Breaker (Q3) is in the
OFF
position.
2
Switch
ON
every external battery cabinet’s breaker (Q5).
3
Switch
ON
the Input Breaker (Q1), Bypass Breaker (Q2) and Output Breaker (Q4).
4
After you switch on the Input Breaker (Q1) and Bypass Breaker (Q2), each auxiliary
power card’s LED indicator will illuminate green and the following status will occur
simultaneously.
(1) The system and each power module will start initialization. After each power
PRGXOH¿QLVKHVLQLWLDOL]DWLRQHDFKSRZHUPRGXOH¶VIDQVZLOOVWDUWUXQQLQJHDFK
power module will start establishing DC BUS voltage and each power module’s
LED indicator will illuminate green.
(2) Each parallel communication card’s LED indicator will illuminate red first and
then each card will start initialization. After initialization, the master parallel
communication card’s LED indicator will illuminate green and the backup
communication card’s LED indicator will illuminate yellow.
For the locations of the parallel communication cards, auxiliary power cards, power
modules and their LED indicators, please refer to
)LJXUH
.
5
The
LCD
initial
screen
(see
)LJXUH
) will appear within 40 seconds after the Input
Breaker (Q1) and Bypass Breaker (Q2) are turned on.
)LJXUH/&',QLWLDO6FUHHQ
Содержание DPH-300K
Страница 8: ......
Страница 14: ......
Страница 60: ......
Страница 76: ......
Страница 227: ...8 1 8 Optional Accessories 8 Optional Accessories ...
Страница 230: ......
Страница 231: ...9 1 9 Maintenance Maintenance ...
Страница 233: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1 A1 ...
Страница 236: ......
Страница 237: ...A2 1 Appendix 2 Warranty Warranty A2 A2 ...
Страница 240: ... ...