OFF
the Manual Bypass Breaker (Q3).
7
Tap the ON/ OFF Button (
) and the following screen will pop up to ask if you want
to power on the UPS’s inverter. Please select '
YES
'.
Bypass
MEASUREMENT
Power Flow
UPS-1.1
SETUP
MAINTENANCE
EVENT LOG
POWER ON ?
No
Yes
LOG IN
User
10:15
May 25,2018
)LJXUH3RZHURQ5HPLQGHU6FUHHQ
8
After selection of '
YES
' to start up the UPS’s inverter, each power module will start
up and perform self-inspection. At the same time, the system begins synchronization
with the bypass AC source. After the self-inspection is completed, the UPS will
automatically transfer to run in On-Line mode, the tri-color LED indicator will illuminate
green and the following screen will appear.
On-Line
POWER FLOW
Maintenance
Bypass
Bypass
Mains
90 %
5 mins
Load
30 %
MEASUREMENT
Power Flow
UPS-1.1
SETUP
MAINTENANCE
EVENT LOG
LOG IN
User
Power Flow
Summary
EMS
System Status
10:15
May 25,2018
)LJXUH2Q/LQH0RGH6FUHHQ