3.1.13 ECO Mode_ Single Input_ Parallel Units
To activate ECO mode, please refer to
(&20RGH6WDUWXS3URFHGXUHV
,
0DLQ
6FUHHQ
and
0RGH6HWWLQJ
.
In ECO mode (parallel), when each parallel UPS’s bypass input voltage and frequency
are within the range of rating voltage ±10% and rating frequency ±3Hz, each parallel UPS
works in Bypass mode; otherwise, each parallel UPS runs in On-Line mode. During ECO
mode (parallel), each UPS’s tri-color LED illuminates green and each UPS’s LCD shows the
text '
ECO
' in the upper right corner. Please see
)LJXUH
for the path of electrical power
through the parallel UPSs in ECO mode.
MAIN
LOAD
MAIN
1
2
Q1
Q2
Q4
Q3
Q5
Batteries
Rectifier
Inverter
Static Switch
Q1
Q2
Q4
Q3
Q5
Batteries
Rectifier
Inverter
Static Switch
)LJXUH(&20RGH'LDJUDPB6LQJOH,QSXW3DUDOOHO8QLWV