5 - 4 3
5
Installation and Wiring
5.8.1 Power Module Installation
After firmly installing the UPS on the designated installation area according to the
instructions stated in
836,QVWDOODWLRQ
, continue with the following steps to install the
power module (optional) into the UPS.
WARNING:
2QO\TXDOL¿HGVHUYLFHSHUVRQQHOFDQSHUIRUPWKHIROORZLQJSRZHUPRGXOH
installation procedures.
2. The power module is heavy (> 36 kg (79.4 lb)). At least two people are
required for handling.
3. Please follow your UPS capacity to install the correct number of power
modules. Please refer to the table below.
UPS
Capacity
100kVA/
100kW
150kVA/
150kW
200kVA/
200kW
250kVA/
250kW
300kVA/
300kW
Power
Module Q’ty
2
3
4
5
6
4. Please install the power modules from the top layer of the power module
slot to the bottom layer of the power module slot in sequence.
1
&RQ¿UPWKDWWKHSRZHUPRGXOH¶VVZLWFKLVLQWKHORZHUSRVLWLRQ
).
)LJXUH&RQ¿UPWKH3RZHU0RGXOH¶V6ZLWFKLQWKH/RZHU3RVLWLRQ
2
Take out the two bracket ears, four M6 screws and eight M4 screws from the power
module’s package.
3
Use the provided eight M4 screws to fix the provided two bracket ears on the two
sides of the power module. Please refer to
)LJXUH
.
Содержание DPH-300K
Страница 8: ......
Страница 14: ......
Страница 60: ......
Страница 76: ......
Страница 227: ...8 1 8 Optional Accessories 8 Optional Accessories ...
Страница 230: ......
Страница 231: ...9 1 9 Maintenance Maintenance ...
Страница 233: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1 A1 ...
Страница 236: ......
Страница 237: ...A2 1 Appendix 2 Warranty Warranty A2 A2 ...
Страница 240: ... ...