background image

Installation and 
user manual

EATON 5S

850/1200/1600

Содержание 5S 1200

Страница 1: ...Installation and user manual EATON 5S 850 1200 1600 ...

Страница 2: ... 614 06819 00 2 3 1 5 EATON 5S Packaging l Before installing the Eaton 5S read the booklet 3 containing the safety instructions to be respected Then follow the instructions given in this manual 2 Caution ...

Страница 3: ...3 614 06819 00 Quick start B C A 1200 1600 850 D ...

Страница 4: ...e life is reduced by 50 for every ten degrees above 25 C The battery elements must be replaced exclusively by qualified personnel risk of electrocution with new elements approved by Eaton to ensure correct operation of the UPS The battery must be disposed of in accordance with applicable regulations To remove the battery elements shut down the UPS button 6 OFF remove the power cord and proceed as ...

Страница 5: ...max 7 3 A max Leakage current 0 4 mA Input protection 10 A resettable circuit breaker Transfer time 5 ms typical Telephone surge protection Tel ISDN ADSL Ethernet Sealed lead acid battery 12 V 9 Ah 2 x 12 V 7 Ah 2 x 12 V 9 Ah Automatic battery test Once a week Average battery life 4 years typical depending on temperature and amount of discharge cycles Operating temperature 0 to 35 C Storage temper...

Страница 6: ...UPS can be installed in horizontal vertical position or placed in Rack 2U optional kit 2 Description AVR Min Hz kVA kW 6 7 8 6 ON OFF button for the battery backup outlets 7 Scroll down 8 Mute alarm LCD 16 15 14 17 11 10 9 12 13 9 UPS ON 10 AVR mode 11 Battery mode 12 Internal fault 13 Output load level 14 Battery level 15 Input measurements 16 Output measurements 17 Measuring unit Outlets 20 19 1...

Страница 7: ...Register for the warranty on powerquality eaton com 4 Master and EcoControl outlets operating procedure In order to limit energy consumption of peripherals scanner printer in standby mode the Eaton 5S is equipped with EcoControl outlets that are dependent on the Master outlet When the main application supplied by the Master outlet computer is shut down the EcoControl outlets are automatically deac...

Страница 8: ...Filtered outlets 18 without battery backup Equipment connected to these outlets is supplied as soon as the AC cord 4 is plugged in They are not affected by button 6 Battery backup outlets 19 Equipment connected to these outlets is supplied as soon as button 6 turns green see figure D These outlets can be turned on even if the UPS is not connected to AC power button 6 flashes 6 UPS setting through ...

Страница 9: ...er supplied Call after sales support 6 EcoControl outlets keep powered when main application Master outlet is stopped EcoControl function is not activated or not properly set Activate or set properly EcoControl function using the software provided with the product 8 Troubleshooting AC power disturbance If AC power is disturbed or fails the UPS continues to operate on battery power Button 6 flashes...

Страница 10: ......

Отзывы: