24
3.5
Holing
Make holes according to the diagram and piping method (upper, lower piping) in the raised
floor or ceiling to allow the pipes to pass through.
The outer layer of the pipe is covered with an insulation layer to reduce damage from external
collisions or unintentional condensation that can lead to dripping. Leave a margin of about
13mm for the hole diameter. The figure below shows the position of the power cable and
signal cable at the door.