InfraSuite - CoolDoor
18
Chapter 3 : Installation
WARNING:
1. Only service personnel can perform the following installation procedures. No
installation, piping or handling should be performed without authorization, so
as to avoid equipment damage and personal injury.
2. The high voltage in the equipment is potentially fatal! The inner components
have potential dangers and only qualified service personnel can perform
wiring.
3.1
Installation Site
When planning the installation site for the cooling unit, you must take the following into
consideration so as to guarantee the best efficiency.
•
Environmental requirements:
The installation site must allow for moving the
equipment into and out of the site; the flooring must bear the weight of the equipment;
and there must be a sufficient space for maintenance, operation, and pipe repair. The
cooling unit can only be located indoors, and the indoor environment must be isolated
from the outside air to avoid temperature and humidity interference. The outside
humidity entry must be minimized in accordance with the local or national regulations
so as to avoid the increase of operation costs due to loss of cooling capacity.
•
Humidity and heat source:
Implement water-proofing and heat insulation engineering
for the indoor environment so as to isolate the outside humid hot air.
NOTE:
The unit cannot humidify or automatically de-humidify. If the humidity of the
installation environment exceeds the operation scope (refer to
5.2 Operating
Temperature & Humidity
), the condensation of the water on the coil and pipes
may lead to trigger an alarm.
•
Noise impact:
At a high load, the operation of this cooling unit may produce loud noise.
Therefore, it is not suitable to install the unit close to offices.
•
Input power:
In connecting the power supply, make sure that the power conforms to
the rated value, and that the power distribution device is sufficient to satisfy the load
requirement. Inspect the rated values of each unit and make sure they have been
properly grounded. One branch circuit or power distribution device can only be
connected with one cooling unit.