InfraSuite - CoolDoor
60
value can be set according to
customer needs. When the dry ball
temperature on the remote sensor is
lower than the configured value, an
alarm will be generated.
5. Remote Air T Low: It can be turned on
by
☑
; an appropriate temperature
value can be set according to
customer needs. When the dry ball
temperature on the remote sensor is
lower than the configured value, an
alarm will be generated.
6. Remote Air DP T High: It can be
turned on by
☑
; an appropriate
temperature value can be set
according to customer needs. When
the wet ball temperature on the
remote sensor is higher than the
configured value, an alarm will be
generated.
7. Water In T High: It can be turned on
by
☑
; an appropriate temperature
value can be set according to
customer needs. When the water
inlet temperature is higher than the
configured value, an alarm will be
generated.
8. Water In T Low: It can be turned on
by
☑
; an appropriate temperature
value can be set according to
customer needs. When the water
inlet temperature is lower than the
configured value, an alarm will be
generated.
9. Water Flow Rate Low: It can be
turned on by
☑
; an appropriate
temperature value can be set
according to customer needs. When
the water inflow is lower than the
configured value, an alarm will be
generated.
10. Water Flow Rate Low: It can be
turned on by
☑
; an appropriate
temperature value can be set
according to customer needs. When