Remote temperature (humidity) sensors have been correctly connected and set up
in appropriate locations.
The water leakage testing line has been correctly deployed.
Mechanical Connection
The pipes and valves are free of rupture or damage.
Is the control valve/electric shut-off valve installed and is the wiring correct?
Is the flow meter installed and is the wiring correct?
The temperature of external water supply is steady.
The external water supply pressure is correct.
5.2
Operating Temperature & Humidity
Use auxiliary dehumidification equipment or air conditioners to adjust the indoor temperature
and humidity when setting up the equipment room. When applied to low load conditions and
high humidity conditions, use auxiliary dehumidification equipment to adjust the humidity.
WARNING:
If the indoor humidity is too high and the chilled water temperature is too low,
condensation around the coil may generate too much condensate, which will lead
to leakage on the indoor floor. Ensure that the chilled water temperature is always
higher than the dew point temperature of the indoor environment.