5. Fan P Gain: Pressure control can be
chosen for fan accessories. The fan
controls the air volume according to
the pressure between the IT Rack
and CoolDoor, and the adjustment
method is controlled according to the
proportional P.
6. Fan I Gain: The fan accessories can
choose pressure control, the fan
controls the air volume according to
the pressure between the IT Rack
and CoolDoor, and the adjustment
method is controlled according to the
integral time I.
7. Min Fan Speed: The minimum fan
speed, even without any load, will still
run at the lowest speed.
8. Leak. BV-OFF: When ON is selected,
and the Leak Detection Sensor
detects water leakage, the ball valve
and Shut Off Valve (optional) will be
closed at the same time to avoid
worsening of the leakage.
9. Auto Recover: When ON is selected,
after the CoolDoor suffers a complete
power outage, the power will recover
and still maintain the working mode
before the power outage.
10. Turbo boost: When ON is selected,
the mutual backup mode provided by
Delta CoolDoor is activated. When
the ball valve or fan is abnormal
during operation, it will be supported
by the surrounding CoolDoors.
11. LED Light Bar: You can turn on or turn
off the Light Bar function below.
12. Fire. Cut-Off: When ON is selected,
and the CoolDoor fire and smoke dry
contact receives a status transition
signal, the CoolDoor will execute the
standby state, and the fan and ball
valve will be completely closed.