InfraSuite - CoolDoor
58
Set Alarm
Main menu
→
Setting
→
Set Alarm
,
press
key to enter.
This page can be used by customers to
set Alarms according to their needs
Select content:
1. Sensor Alarm
2. Actuator Alarm
3. Out of Range
Sensor Alarm
Main menu
→
Setting
→
Set Alarm
→
Sensor Alarm
, press
key to
enter.
The sensor alarm page can be adjusted
by the user, as described below
1. Leak SEN: The sensitivity of the Leak
Detection Sensor can be set;
selection is off/low/medium/high
2. Water Inlet: You can choose whether
to produce an alarm when the inlet
water
temperature
sensor
is
abnormal.
3. Water Outlet: You can choose
whether to produce an alarm when
the outlet water temperature sensor
is abnormal (the outlet water
temperature sensor is an optional
accessory).
4. Remote Sensor: Delta CoolDoor can
detect the temperature and humidity
of the channel environment, and you
can choose whether to produce an
alarm when the temperature and
humidity sensors are abnormal (the
remote temperature sensor is an
optional accessory).
5. Condensation: Select
☑
; when the
environmental dew point is too high
and there is a risk of condensation, an
alarm will be generated. This function
must be used with the Remote
Sensor option.
Sensor Alarm
Actuator Alarm
Out of Range
Leak SEN. : High
Water Inlet T:☑
Water Outlet T:☑
Remote Sensor :☑
Condensation :☑
Fire Detection:☑