11
1.6
Design Capacities
The range of design conditions shown in the above table will vary with the user's design
ability, water volume, and different return air temperatures. It is recommended that you
contact Delta service personnel and provide them with detailed calculation parameters in
the design.
CoolDoor
Unit
Quantity
Duct connection
Rack Unit Height
U
42U‐48U
Rack Unit Width
mm
600-800mm
Rack Unit Deep
Inch
12
Water Side
Fluid Type
Water or Glycol
Fluid Flow
GPM
<23.8
Pressure Drop (coil + ball valve)
Psi
9.4
Inlet Temperature
°F
53.6~68
Cooling Capacity
kW
<53
Max Allowable Inlet Pressure
Psig
142
Air Side
Air Volume
CFM
2000~4016
Cabinet
Approximate Shipping Weight
Lbs
367-385
Approximate Operating Weight
Lbs
198-216
Electricity
Power Supply
200-240V / 1N / 50,60Hz
MCA
A
4.5
MOP
A
5.5