Object Name
Object Ref
Default
Description
Button 1 to 8
MV1010 to MV1017
NotUsed_
Options for the buttons of the
LINKnet network sensor used
with the enteliZONE controller.
Occupancy Configuration Objects
Object Name
Object
Ref
Default
Description
Local Schedule
SCH1
N/A
Local schedule object on the controller. It is
used to provide local scheduled operations
based on a 7-day recurring schedule.
Exception scheduling is not supported.
Remote Sched-
ule
MV1
NotUsed_
An object that can be written over the network
to provide a remote schedule input.
OccOvrdButton
MV2
NotUsed_
Network sensor button used as an occupancy
override button.
OccToggle But-
ton
MV3
NotUsed_
Network sensor button to toggle between
standby and occupied modes during scheduled
occupancy periods.
OccMotion
MV4
NotUsed_
Motion sensor that is integrated into the
network sensor. Object can be set up to be a
maintained contact or a momentary contact
type.
OccMaintained
Contact
MV5
NotUsed_
Used for any maintained contact signal type
like a hotel keycard holder, manual switch or
mechanical time clock input.
Occupancy
Mode
MV800
Unoccupied_
Occupancy modes.
OccIndicator
MV806
NotUsed_
Used to display the occupancy icon on the
network sensor LCD screen.
Содержание eZFC-424R4-24
Страница 1: ...eZFC 424R4 24 Application Guide Edition 2 6...
Страница 67: ...enteliZONE Sequence of Operations Page 66 of 84 eZFC 424R4 24 Application Guide Edition 2 6...
Страница 70: ...eZFC 424R4 24 Application Guide Edition 2 6 Page 69 of 84...
Страница 71: ...enteliZONE Sequence of Operations Page 70 of 84 eZFC 424R4 24 Application Guide Edition 2 6...