eZFC-424R4-24 Application Guide
Edition 2.6
Page 25 of 84
Field Name
Description
Parent
Address
(enteliWEB
only)
This field is enabled when the Child Controller box is checked. Enter the
parent's BACnet address in this field. If you are setting up a parent controller,
leave this field at its default zero value.
If the parent’s BACnet address changes in the future, you must manually
update this value to match the new address.
Parent Child
Address
(ORCAview
only)
If this controller reports to a parent controller, enter the parent’s BACnet
address in this field. In all other cases, including setting up a parent controller,
leave this field at its default zero value.
If the parent’s BACnet address changes in the future, you must manually
update this value to match the new address.
The child controller polls these variables from its parent controller:
l
HeatCoolLoad (AV802)
l
OccupancyMode (MV800)
l
DemandCtrlVent (AV813)
l
ManualFanSpeedCmd (AV17)
l
FanMode (BV1)
When FanMode is set to Automatic in the parent controller, the child
controller’s fan speed is controlled automatically based on demand. When
FanMode is set to Manual, the child controller’s fan speed follows the
ManualFanSpeedCmd value polled from the parent. In this mode, local fan
speed switch or stat fan control button will be suppressed.
Содержание eZFC-424R4-24
Страница 1: ...eZFC 424R4 24 Application Guide Edition 2 6...
Страница 67: ...enteliZONE Sequence of Operations Page 66 of 84 eZFC 424R4 24 Application Guide Edition 2 6...
Страница 70: ...eZFC 424R4 24 Application Guide Edition 2 6 Page 69 of 84...
Страница 71: ...enteliZONE Sequence of Operations Page 70 of 84 eZFC 424R4 24 Application Guide Edition 2 6...