eZFC-424R4-24 Application Guide
Edition 2.6
Page 37 of 84
Setting Up Other Outputs
This topic describes how to set up supporting outputs like occupancy indicator on the Local Outputs
tab of the enteliZONE configuration page.
Set Up an Output
1. In the
Function
field, select the option that applies to your setup:
Function
Select this option if you
are:
OccIndicator_
Setting up an occupancy
output signal.
Any one of the following: ElectricBaseboard_,
HydronicBaseboard_
Controlling radiant heating
equipment.
2PipeChangeOverValve
Controlling a binary water
valve.
GCL-controlled AO_*
Creating a custom AO object.
GCL-controlled BO_*
Creating a custom BO object.
* Available only with programmable enteliZONE models and only on output terminals that
support AO or BO objects.
For a list of output configuration software objects that correspond to each function, see the
Output Configuration Objects topic
.
2. In the
Stage
field, for the radiant heating equipment, select the radiant heating equipment's
heat stage in the control sequence. If you are using ORCAview,select the heat stage in the
Output Stage
field.
Function
Stage or Output Stage
OccIndicator_
OccIndicator_
is the default
option.
Any one of the following: ElectricBaseboard_,
HydronicBaseboard_
Select one:
Heat1_
,
Heat2_
or
Heat3_
.
2PipeChangeOverValve
HeatCoolChangeOverCmd
is the
default option.
GCL-controlled AO_
None_
is the default option.
GCL-controlled BO_
None_
is the default option.
Содержание eZFC-424R4-24
Страница 1: ...eZFC 424R4 24 Application Guide Edition 2 6...
Страница 67: ...enteliZONE Sequence of Operations Page 66 of 84 eZFC 424R4 24 Application Guide Edition 2 6...
Страница 70: ...eZFC 424R4 24 Application Guide Edition 2 6 Page 69 of 84...
Страница 71: ...enteliZONE Sequence of Operations Page 70 of 84 eZFC 424R4 24 Application Guide Edition 2 6...