eZFC-424R4-24 Application Guide
Edition 2.6
Page 49 of 84
Set Up the Button Elements
On the LINKnet I/O tab, in the Button Options section, next to the button you want to program,
select one of the following functions that you want to assign to that button:
Function
Recommended
corresponding
DNS-24L button
Select this option if you want to:
NotUsed_
Not applicable
Designate custom button behavior using GCL or
if you want a blank button.
OccupancyOff_
Button 1
Turns on the standby occupancy mode.
In the additional settings, in the
PushButtonOvrdTime
field, you can enter how
long the button override should last.
OccupancyOn_
Button 2
Turns on the occupied mode.
In the additional settings, in the
PushButtonOvrdTime
field, you can enter how
long the button override should last.
OccupancyToggle_
Button 1 (DNS
Fan model)
Toggle between standby and occupied modes
during scheduled occupancy periods.
When pushed during unoccupied mode it starts
an occupancy override timer. When an override
has been activated, pushing the button again will
cancel the override and reset the override timer
back to zero.
In the additional settings, in the
PushButtonOvrdTime
field, you can enter how
long the button override should last.
TempUnitsToggle_
Not applicable
Recommended for use with the eZNS network
sensor. Toggles between displaying the
temperature in Celsius and the temperature in
Fahrenheit.
Содержание eZFC-424R4-24
Страница 1: ...eZFC 424R4 24 Application Guide Edition 2 6...
Страница 67: ...enteliZONE Sequence of Operations Page 66 of 84 eZFC 424R4 24 Application Guide Edition 2 6...
Страница 70: ...eZFC 424R4 24 Application Guide Edition 2 6 Page 69 of 84...
Страница 71: ...enteliZONE Sequence of Operations Page 70 of 84 eZFC 424R4 24 Application Guide Edition 2 6...