![Delta Controls eZFC-424R4-24 Скачать руководство пользователя страница 63](http://html1.mh-extra.com/html/delta-controls/ezfc-424r4-24/ezfc-424r4-24_application-manual_2475119063.webp)
enteliZONE Sequence of Operations
Page 62 of 84
eZFC-424R4-24 Application Guide
Edition 2.6
The heating or cooling output is limited by the discharge air limited controller that maintains a
maximum limit above the CurrentHeatSetPoint (AV800) in heating, and a minimum limit below the
CurrentCoolSetpoint (AV801) during cooling. The maximum limit is calculated by adding the
discharge air temperature high limit setpoint differential (DATHiLimitSetpointDiff) to the
CurrentHeatSetPoint, and the minimum limit is calculated by subtracting the discharge air
temperature low limit setpoint differential from the CurrentCoolSetpoint.
Limiting the ducted heating and cooling stages ensures the temperature differential between space
air and supply air is not large enough to cause hot air to build up near the ceiling. Limiting heating
and cooling outputs also encourages cold air to spread out via the diffuser and mix well with the
room air. Cold air that drops down without mixing can create complaints of cold drafts.
Fan (Fancoil)
The section describes the supply fan sequences supported by the fan coil algorithm for duct heating
and cooling.
Duct heat or cooling will only be enabled in the algorithm when a supply fan has been
configured.
Manual Fan Speed Control
The algorithm allows you to manually change the fan speed when you set up a fan speed control
switch as an input or on your network sensor.
In both manual and automatic fan speed control, when you switch between fan stages, there is a 1-
second delay where the prior stage turns off before the next stage can turn on.
If the fan is turned off while in manual mode, when the space temperature falls outside of the
unoccupied setpoints, the algorithm will override the fan to prevent temperature extremes.
Automatic Fan Speed Control
When there is no manual fan speed control switch configured, the algorithm assumes automatic
fan speed control. In automatic fan speed mode, the occupancy state of the space, heat/cool
demand and the constant fan mode statuses determine when a fan runs and its speed: the
algorithm can either run the fan continuously, or intermittently (runs only when there is a heat or
cooling demand). For a fuller description of the various constant fan modes, see the
.
Run the fan continuously if you want the fan coil to provide both ventilation and temperature control.
If the fan coil does not provide ventilation, then running the fan intermittently will save energy. While
the fan is in constant mode:
Содержание eZFC-424R4-24
Страница 1: ...eZFC 424R4 24 Application Guide Edition 2 6...
Страница 67: ...enteliZONE Sequence of Operations Page 66 of 84 eZFC 424R4 24 Application Guide Edition 2 6...
Страница 70: ...eZFC 424R4 24 Application Guide Edition 2 6 Page 69 of 84...
Страница 71: ...enteliZONE Sequence of Operations Page 70 of 84 eZFC 424R4 24 Application Guide Edition 2 6...