eZFC-424R4-24 Application Guide
Edition 2.6
Page 33 of 84
Local Outputs Tab
Setting Up a Fan Coil or Heat Pump Output
This topic describes how to set up fan coil outputs (fan, heat and cooling) on the Local Outputs tab
of the enteliZONE configuration page.
The eZFC-424R4-24 and eZ-440R4-230 enteliZONE controllers support the fan coil and heat
pump algorithms.
The fan coil and heat pump algorithms support:
l
3-speed fan stages (Fan1, Fan2 and Fan3) or ECM (Electronically Commutated Motor) fan
(Fan1)
l
3 heat stages: Heat1, Heat2 and Heat3
l
2 cooling stages: Cool1, Cool2
l
Single heat/cool stages: HeatCool1 and HeatCool2
For more information about the enteliZONE algorithm's sequence of operations, go to the
help.
Set up a Fan Coil Output
1. In the Function field, make the following selections depending on the type of fan coil unit you
are setting up: (start a new line for every additional heat/cool/fan stage).
Each numbered line should correspond to the physical output used to connect to the output
device.
Duct heat or cooling will only be enabled in the algorithm when a supply fan is configured.
For a list of output configuration software objects that correspond to each function, see the
Output Configuration Objects help topic
Examples of Systems
Function
Stage or Output
Stage
4-pipe (duct heat) fan coil
HydronicDuct_
Heat1_
HydronicDuct_
Cool1_
SupplyFan_
Fan1_
2-pipe (duct heat) fan coil
HydronicDuct_
HeatCool1_
SupplyFan_
Fan1_
Содержание eZFC-424R4-24
Страница 1: ...eZFC 424R4 24 Application Guide Edition 2 6...
Страница 67: ...enteliZONE Sequence of Operations Page 66 of 84 eZFC 424R4 24 Application Guide Edition 2 6...
Страница 70: ...eZFC 424R4 24 Application Guide Edition 2 6 Page 69 of 84...
Страница 71: ...enteliZONE Sequence of Operations Page 70 of 84 eZFC 424R4 24 Application Guide Edition 2 6...