![Delta Controls eZFC-424R4-24 Скачать руководство пользователя страница 31](http://html1.mh-extra.com/html/delta-controls/ezfc-424r4-24/ezfc-424r4-24_application-manual_2475119031.webp)
Local Inputs Tab
Page 30 of 84
eZFC-424R4-24 Application Guide
Edition 2.6
5. (enteliWEB only) The Input Name field displays the object's name. You can change this
name by clearing the field and entering a new name.
For more information about using CO2 levels to trigger occupancy events, see the
Setting Up a Fan Speed Switch
This topic describes how to set up a fan speed switch using the Local Inputs tab on the
configuration page.
The fan coil algorithm supports up to 3 fan speeds.
Set Up a Fan Speed Switch
1. Next to the input number that you’ve assigned to the switch, in the Function field, select
FanSpdCtrl
.
2. Leave the Action/Scale field blank.
3. In the additional settings, do one of the following steps:
l
For a simple on/off switch, select
FanSpdSwitchOffResistance
and
FanSpdSwitchFan1Resistance
. Using the switch specifications, enter the
resistance values.
l
For multiple fan speed control, select the boxes that correspond to the different
speeds available on your switch.
4. (enteliWEB only) The Input Name field displays the object's name. You can change this
name by clearing the field and entering a new name.
Setting Up a Fan Coil 2-Pipe Changeover Sensor
1. Next to the input number that you’ve assigned to the switch, in the Function field, select
2PipeChangeOverTemp_
.
2. Under Scale,
Temp_10K3DegC
or
Temp_10K3DegF
is selected, depending on the
temperature units set up on the General tab.
3. The Input Name field displays the object's name. You can change this name by clearing the
field and entering a new name.
For more information about the auto changeover works, see the
Содержание eZFC-424R4-24
Страница 1: ...eZFC 424R4 24 Application Guide Edition 2 6...
Страница 67: ...enteliZONE Sequence of Operations Page 66 of 84 eZFC 424R4 24 Application Guide Edition 2 6...
Страница 70: ...eZFC 424R4 24 Application Guide Edition 2 6 Page 69 of 84...
Страница 71: ...enteliZONE Sequence of Operations Page 70 of 84 eZFC 424R4 24 Application Guide Edition 2 6...