eZFC-424R4-24 Application Guide
Edition 2.6
Page 29 of 84
4. (enteliWEB only) The Input Name field displays the object's name. You can change this
name by clearing the field and entering a new name.
With the OccToggleButton option, With the OccToggleButton option, it is recommended
to display the occupancy status on your network sensor. The occupancy status allows the
user to determine if a button press will start an override or cancel an active override.
Multiple Temp+Occ Inputs
You can set up multiple
OccOvrdButton
and
OccToggleButton
inputs
and by default the algorithm will calculate the average of all these temperature inputs. With multiple
occupancy inputs, the value will reflect the last value written.
Setting Up a Hardwired CO2 Sensor
This topic describes how to set up a carbon dioxide sensor using the Local Inputs tab on the
configuration page.
If you are setting up a LINKnet DNS-24L or eZNS network sensor to provide occupancy
input, use the LINKnet I/O tab on the configuration page.
Set Up a Hardwired CO2 Sensor
1. Wire your sensor to the controller's physical input.
2. Next to the input number that you've assigned to the input, in the Function field, select
SpaceCO2_
. The default option in the Action/Scale column is CO2 0-2000ppm.
3. If you are using demand controlled ventilation with the CO2 sensors, in the additional
settings,
l
In the
DemandVentEnable
field, select Enabled or On (enteliWEB only).
l
In the
CO2DemandVentSetpoint
field, enter the CO2 setpoint value. Levels higher
than this setpoint will maintain the demand for ventilation.
4. In the additional settings, if you are using CO2 sensors to determine occupancy,
l
(enteliWEB only) In the CO2 Occupancy On Setpoint field, enter the CO2 setpoint
value that will trigger an occupancy event. To disable CO2-based occupancy
detection, set this value to 2000 ppm.
l
(enteliWEB only) In the CO2 Occupancy Off Setpoint field, enter the CO2 setpoint
value that will cancel an occupancy event.
Содержание eZFC-424R4-24
Страница 1: ...eZFC 424R4 24 Application Guide Edition 2 6...
Страница 67: ...enteliZONE Sequence of Operations Page 66 of 84 eZFC 424R4 24 Application Guide Edition 2 6...
Страница 70: ...eZFC 424R4 24 Application Guide Edition 2 6 Page 69 of 84...
Страница 71: ...enteliZONE Sequence of Operations Page 70 of 84 eZFC 424R4 24 Application Guide Edition 2 6...