![Delta Controls eZFC-424R4-24 Скачать руководство пользователя страница 28](http://html1.mh-extra.com/html/delta-controls/ezfc-424r4-24/ezfc-424r4-24_application-manual_2475119028.webp)
eZFC-424R4-24 Application Guide
Edition 2.6
Page 27 of 84
When setting up a temperature sensor, majority of the cases would require you to select
Temp_10K3DegC
or
Temp_10K3DegF
as an option under
Action/Scale
, depending on
the temperature units set up on the General tab.
3. If you had selected the
DischargeAirTemp_
option, in the additional settings, in the
DATHiLimitSetpointDiff and DATLowLimitSetpointDiff fields, enter the discharge air
temperature high limit and low limit setpoints differentials respectively.
4. (enteliWEB only) The Input Name field displays the object's name. You can change this
name by clearing the field and entering a new name.
Multiple Space Temperature Inputs
You can set up multiple
SpaceTemp
inputs and by default the algorithm will calculate the
average of all inputs and assign that value to the AV1 object.
Setting Up a Hardwired Occupancy Input
This topic describes how to set up an occupancy input using the Local Inputs tab on the
configuration page.
Occupancy inputs can either be maintained-contact or momentary contact types. Occupancy
overrides can share the same input as the temperature sensor.
See the sequence of operations topic to learn more about
in the algorithm.
If you are setting up a LINKnet DNS-24L or eZNS network sensor to provide occupancy
input, use the LINKnet I/O tab on the configuration page.
Set Up a Hardwired Occupancy Input
1. Next to the input number that you've assigned to the input, in the Function field, select one or
more of the following options:
Function
Select this option if you are using a:
OccMotion_
Hardwired latching, momentary contact sensor type, or a
network sensor with an integrated motion sensor and want
to enable it for occupancy control.
OccMaintainedContact_
Any maintained contact device like a hotel keycard holder,
manual switch or mechanical time clock input.
Содержание eZFC-424R4-24
Страница 1: ...eZFC 424R4 24 Application Guide Edition 2 6...
Страница 67: ...enteliZONE Sequence of Operations Page 66 of 84 eZFC 424R4 24 Application Guide Edition 2 6...
Страница 70: ...eZFC 424R4 24 Application Guide Edition 2 6 Page 69 of 84...
Страница 71: ...enteliZONE Sequence of Operations Page 70 of 84 eZFC 424R4 24 Application Guide Edition 2 6...