Convention
Power indicator
pattern
Condition
CAUTION: When correcting a PSU mismatch, replace only the
PSU with the flashing indicator. Swapping the opposite power
supply unit to make a matched pair can result in an error
condition and unexpected system shutdown. To change from
a High Output configuration to a Low Output configuration or
vice versa, you must power down the system.
CAUTION: AC power supplies support both 220 V and 110 V
input voltages with the exception of Titanium power supplies,
which support only 220 V. When two identical power supplies
receive different input voltages, they can output different
wattages, and trigger a mismatch.
CAUTION: If two power supplies are used, they must be of the
same type and have the same maximum output power.
CAUTION: Combining AC and DC power supplies is not
supported and triggers a mismatch.
E
Not lit
Power is not connected.
Figure 8. DC power supply unit status indicator
18