Expanded operating temperature
NOTE: Outside the standard operating
temperature (10°C to 35°C), the system can
operate continuously down to 5°C or as high
as 40°C.
For temperatures between 35°C and 40°C, de-
rate maximum allowable temperature by 1°C per
175 m above 950 m (1°F per 319 ft).
< 1% of annual operating hours
–5°C to 45°C at 5% to 90% RH with 29°C dew
point.
NOTE: Outside the standard operating
temperature (10°C to 35°C), the system can
operate down to –5°C or up to 45°C for a
maximum of 1% of its annual operating hours.
For temperatures between 40°C and 45°C, de-
rate maximum allowable temperature by 1°C per
125 m above 950 m (1°F per 228 ft).
Expanded Operating Temperature
Restrictions
• Do not perform a cold startup below 5°C.
• The operating temperature specified is for a maximum
altitude of 3050 m (10,000 ft).
• Processors between 65 W to 120 W including 105 W
(E5-2660;E5-2650), 90 W (E5-2640), 85 W (E5-2630,
E5-2620, E5-2609, E5-2603) are all supported.
• Processors below 65 W(E5-2630v3, E5-2650v3) and
the 120 W processor are not supported.
• Internal 2.5 inch hard drives are not supported.
• Redundant power supplies are required.
• Non Dell qualified peripheral cards and/or peripheral
cards greater than 25 W are not supported.