AC Power Cord Specifications for a J-EX8200 Switch
Each AC power supply has a single AC appliance inlet located on the power supply that
requires a dedicated AC power feed. Sites can distribute power through a main conduit
that leads to frame-mounted power distribution panels, one of which can be located at
the top of the rack that houses the switch.
NOTE:
A jumper cable for each power supply was shipped with your switch.
If your site uses a power distribution unit (PDU) to distribute power to the
rack that houses the switch, you do not have to purchase AC power cords.
If your site does not use a PDU, you need an AC power cord for your geographical location
to connect each power supply on the switch to the power distribution panel. Detachable
AC power cords for the switch are separately orderable as a field-replaceable unit (FRU)
item.
Each detachable AC power cord is 2.5 meters (approximately 8 feet) long. The appliance
coupler at the female end of the cord inserts into the AC appliance inlet on the faceplate
of the AC power supply. The coupler type is C19 as described by the International
Electrotechnical Commission (IEC) standard 60320. The plug at the male end of the
power cord fits into the power source outlet that is standard for your geographical location.
NOTE:
In North America, AC power cords must not exceed 4.5 meters
(approximately 15 feet) in length, to comply with National Electrical Code
(NEC) Sections 400-8 (NFPA 75, 5-2.2) and 210-52 and Canadian Electrical
Code (CEC) Section 4-010(3). The cords shipped with the switch are in
compliance.
Table 39 on page 83 lists the AC power cord specifications for a J-EX8200 switch for the
countries and regions listed in the table.
Table 39: AC Power Cord Specifications for a J-EX8200 Switch
Plug Standards
Electrical Specifications
Country/Region
RA/3/20, IRAM 2073
250 VAC, 16 A, 50 Hz
Argentina
AS/NZS 3112
250 VAC, 15 A, 50 Hz
Australia
BR/3/20, NBR 14136:2002
250 VAC, 16 A, 60 Hz
Brazil
GB 1002
250 VAC, 16 A, 50 Hz
China
CEE (7) VII
250 VAC, 16 A, 50 Hz
Europe (except Italy, Switzerland, and
United Kingdom)
ZA/3, SABS 164/1:1992
250 VAC, 16 A, 50 Hz or 60 Hz
India
83
Chapter 7: Planning Power Requirements
Содержание PowerConnect J-8216
Страница 1: ...Dell PowerConnect J Series J EX8216 Ethernet Switch Hardware Guide Published 2010 10 05 ...
Страница 6: ...vi ...
Страница 16: ...xvi Dell PowerConnect J Series J EX8216 Ethernet Switch Hardware Guide ...
Страница 18: ...2 Dell PowerConnect J Series J EX8216 Ethernet Switch Hardware Guide ...
Страница 78: ...62 Dell PowerConnect J Series J EX8216 Ethernet Switch Hardware Guide ...
Страница 84: ...68 Dell PowerConnect J Series J EX8216 Ethernet Switch Hardware Guide ...
Страница 92: ...76 Dell PowerConnect J Series J EX8216 Ethernet Switch Hardware Guide ...
Страница 96: ...80 Dell PowerConnect J Series J EX8216 Ethernet Switch Hardware Guide ...
Страница 110: ...94 Dell PowerConnect J Series J EX8216 Ethernet Switch Hardware Guide ...
Страница 112: ...96 Dell PowerConnect J Series J EX8216 Ethernet Switch Hardware Guide ...
Страница 158: ...142 Dell PowerConnect J Series J EX8216 Ethernet Switch Hardware Guide ...
Страница 164: ...148 Dell PowerConnect J Series J EX8216 Ethernet Switch Hardware Guide ...
Страница 166: ...150 Dell PowerConnect J Series J EX8216 Ethernet Switch Hardware Guide ...
Страница 172: ...156 Dell PowerConnect J Series J EX8216 Ethernet Switch Hardware Guide ...
Страница 189: ...PART 5 Switch and Component Maintenance Routine Maintenance on page 175 173 ...
Страница 190: ...174 Dell PowerConnect J Series J EX8216 Ethernet Switch Hardware Guide ...
Страница 197: ...PART 6 Returning Hardware Getting Help on page 183 181 ...
Страница 198: ...182 Dell PowerConnect J Series J EX8216 Ethernet Switch Hardware Guide ...
Страница 216: ...200 Dell PowerConnect J Series J EX8216 Ethernet Switch Hardware Guide ...
Страница 228: ...212 Dell PowerConnect J Series J EX8216 Ethernet Switch Hardware Guide ...
Страница 244: ...228 Dell PowerConnect J Series J EX8216 Ethernet Switch Hardware Guide ...
Страница 252: ...236 Dell PowerConnect J Series J EX8216 Ethernet Switch Hardware Guide ...
Страница 253: ...PART 8 Compliance Information Compliance Information on page 239 237 ...
Страница 254: ...238 Dell PowerConnect J Series J EX8216 Ethernet Switch Hardware Guide ...
Страница 259: ...Declarations of Conformity for J EX8216 Switches 243 Chapter 20 Compliance Information ...
Страница 261: ...PART 9 Index Index on page 247 245 ...
Страница 262: ...246 Dell PowerConnect J Series J EX8216 Ethernet Switch Hardware Guide ...
Страница 270: ...254 Dell PowerConnect J Series J EX8216 Ethernet Switch Hardware Guide ...