Parameter
Range
Default
Notes
Cos phi set point
enable
•
Not enabled
•
Enabled
Not
enabled
•
Not enabled
: The controller ignores the
Cos phi set point
analogue input
and Modbus input.
•
Enabled
: During reactive power sharing, the controller uses the
Cos phi
set point
analogue input or Modbus input as the cos phi set point.
Cos phi set point
source
•
External
•
External -> Off
External
•
External
: The controller uses the
Cos phi set point
analogue input or
Modbus input.
•
External ->
Off
: If the
Cos phi set point
analogue input and/or Modbus
input fails (that is, when the input is outside the configured scale), then the
controller ignores the input.
INFO
If an analogue input is configured, the Modbus value for the external offset will reflect the analogue input value. The
Modbus external offset cannot be configured until the analogue input for the external offset is cleared.
6.4.3 External communication using Modbus
If you want to send set point values over Modbus, instead of using the controller internal set points, then you must configure and
activate the set point function on the controller. When the function is active, the controller ignores the internal set points configured in
the parameters and uses the set points it receives over Modbus.
Inputs
Configure the inputs under
Configure > Input/output
. Select the hardware module, then select the input to configure.
INFO
These inputs are only visible if a regulation output (either relay or analogue) is configured.
Table 6.4
Hardware required in addition to the minimum standard controller wiring
Function
I/O
Type
Details
Regulators > GOV > External set
points > Activate external f offset
Digital
input
Pulse
When activated, the controller changes
Configure > Parameters >
Regulators > GOV general configuration > External offset >
Frequency offset enable
to
Enabled
.
Regulators > GOV > External set
points > Deactivate external f offset
Digital
input
Pulse
When activated, the controller changes
Configure > Parameters >
Regulators > GOV general configuration > External offset >
Frequency offset enable
to
Not enabled
.
Regulators > GOV > External set
points > Activate external P set point
Digital
input
Pulse
When activated, the controller changes
Configure > Parameters >
Regulators > GOV general configuration > External offset > P
set point enable
to
Enabled
.
Regulators > GOV > External set
points > Deactivate external P set
point
Digital
input
Pulse
When activated, the controller changes
Configure > Parameters >
Regulators > GOV general configuration > External offset > P
set point enable
to
Not enabled
.
Regulators > AVR > External set
points > Activate external V offset
Digital
input
Pulse
When activated, the controller changes
Configure > Parameters >
Regulators > AVR general configuration > External offset >
Voltage offset enable
to
Enabled
.
Regulators > AVR > External set
points > Deactivate external V offset
Digital
input
Pulse
When activated, the controller changes
Configure > Parameters >
Regulators > AVR general configuration > External offset >
Voltage offset enable
to
Not enabled
.
Regulators > AVR > External set
points > Activate external Q set point
Digital
input
Pulse
When activated, the controller changes
Configure > Parameters >
Regulators > AVR general configuration > External offset > Q
set point enable
to
Enabled
.
DESIGNER'S HANDBOOK 4189340911K UK
Page 188 of 521