Function
Type
Details
Alarm system > State > Any latched
alarm
Continuous Activated if there are any active alarms with active latches in the controller.
Alarm system > State > Any shelved
alarm
Continuous Activated if there are any shelved alarms in the controller.
Alarm system > State > Any out of
service alarm
Continuous Activated if any alarms in the controller are out of service.
Alarm system > State > Any SGB trip
alarm
Continuous
Activated if there is any active alarm in the controller with the alarm action
Trip
shaft generator breaker
.
Note: Only SHAFT generator controllers.
Alarm system > State > Any SCB trip
alarm
Continuous
Activated if there is any active alarm in the controller with the alarm action
Trip
shore connection breaker
.
Note: Only SHORE connection controllers.
Alarm system > State > Any BTB trip
alarm
Continuous
Activated if there is any active alarm in the controller with the alarm action
Trip
bus tie breaker
.
Note: Only BUS TIE breaker controllers.
Any AVR trip alarm
Continuous
Activated if there is any active alarm with the alarm action
Trip AVR
.
Note: Only GENSET, EMERGENCY genset and SHAFT generator controllers.
Any GB + AVR alarm
Continuous
Activated if there is any active alarm with the alarm action
Trip generator
b AVR
.
Note: Only GENSET and EMERGENCY genset controllers.
Any SGB + AVR alarm
Continuous
Activated if there is any active alarm with the alarm action
Trip generator
b AVR
.
Note: Only SHAFT generator controllers.
Any GB + AVR + stop engine alarm
Continuous
Activated if there is any active alarm with the alarm action
Trip generator
b AVR + stop engine
.
Note: Only GENSET and EMERGENCY genset controllers.
Applications
A digital output with an alarm status may be wired to a switchboard light, to help the operator. For example, you can configure a
relay with the
Alarm system > State > Any latched alarm
function, and wire it to a light on the switchboard. When there are any
alarms with active latches, the light is lit. The operator then knows that there are alarms that must be checked and unlatched.
Alarm test
The alarm test activates these outputs. Acknowledging the test alarms deactivates the outputs.
4.6 Horn outputs
4.6.1 Horn output function
Any of the controller's configurable digital outputs can be configured as horn outputs. These horn outputs are typically connected to
an acoustic alarm or visual indicator.
The controller alarm system is in full control of the horn outputs. Other systems, including CustomLogic, cannot control the horn
outputs. If a digital output is configured as a horn output, it cannot be configured for anything else.
DESIGNER'S HANDBOOK 4189340911K UK