4.5.2 Alarm status digital outputs
You can configure a digital output with a function for an alarm status. The controller activates the digital output if the alarm status is
present.
Assign the function to a digital output under
Configure > Input/output
. Select a hardware module with a digital output, then select
the output to configure.
Table 4.9
Alarm status digital output functions
Function
Type
Details
Local > System OK > Status OK
Continuous
Activated if the power supply to PSM3.1 is OK, and all of the controller
hardware module self-checks were OK.
Status OK
is always configured on terminals 3 and 4 of PCM3.1.
Status OK
can also be configured on any other digital output terminals.
This digital output has a safety function. The controller deactivates this output
if there is a problem with the controller.
Alarm system > State > Any warning
alarm
Continuous Activated if there are any warning alarm active in the controller.
Alarm system > State > Any block
alarm
Continuous
Activated if there is any active alarm in the controller with the alarm action
Block
.
Alarm system > State > Any PMS-
controlled stop alarm
Continuous
Activated if there is any active alarm in the controller with the alarm action
PMS-controlled stop
.
Note: Only GENSET and EMERGENCY genset controllers.
Alarm system > State > Any PMS-
controlled open breaker alarm
Continuous
Activated if there is any active alarm in the controller with the alarm action
PMS-controlled open breaker
.
Note: Only SHAFT generator, SHORE connection and BUS TIE breaker
controllers.
Alarm system > State > Any GB trip
alarm
Continuous
Activated if there is any active alarm in the controller with the alarm actions
Trip generator breaker
,
Trip generator breaker and AVR
,
Trip generator
breaker and stop engine
,
Trip generator breaker and AVR and stop engine
,
Trip generator breaker and shutdown engine
and/or
Trip generator breaker
and AVR and shutdown engine
.
Note: Only GENSET and EMERGENCY genset controllers.
Alarm system > State > Any GB trip
and stop alarm
Continuous
Activated if there is any active alarm in the controller with the alarm action
Trip
generator breaker and stop engine
and/or
Trip generator breaker and AVR and
stop engine
.
Note: Only GENSET and EMERGENCY genset controllers.
Alarm system > State > Any GB trip
and shutdown alarm
Continuous
Activated if there is any active alarm in the controller with the alarm action
Trip
generator breaker and shutdown engine
and/or
Trip generator breaker and
AVR and shutdown engine
.
Note: Only GENSET and EMERGENCY genset controllers.
Alarm system > State > Any alarm
Continuous
Activated if there are any acknowledged, unacknowledged or alarms with
active latches in the controller.
Alarm system > State > Any
unacknowledged alarm
Continuous Activated if there are any unacknowledged alarms in the controller.