Table 3.12
[Source] reactive power analogue output functions
Function
Details
[Source] > Reactive power (Q) > [Equipment] | L1 [kvar] The controller outputs the L1 reactive power.
[Source] > Reactive power (Q) > [Equipment] | L2 [kvar] The controller outputs the L2 reactive power.
[Source] > Reactive power (Q) > [Equipment] | L3 [kvar] The controller outputs the L3 reactive power.
[Source] > Reactive power (Q) > [Equipment] | Total
[kvar]
The controller outputs the total reactive power.
[Source] > Reactive power (Q) > [Equipment] | Min.
[kvar]
The controller outputs the reactive power of the phase with the lowest
reactive power.
[Source] > Reactive power (Q) > [Equipment] | Max.
[kvar]
The controller outputs the reactive power of the phase with the highest
reactive power.
[Source] > Reactive power (Q) > [Equipment] | Total [%]
The controller outputs the total reactive power, as a percentage of the
source's nominal reactive power.
[Source] > Reactive power (Q) > [Equipment] | Available
[kvar]
The controller outputs the available reactive power for the source in kvar.
Available reactive power = Nominal reactive power - Total reactive
power
[Source] > Reactive power (Q) > [Equipment] | Available
[%]
The controller outputs the available reactive power for the source, as a
percentage of the source's nominal reactive power. Available reactive
power = Nominal reactive power - Total reactive power
Table 3.13
[Source] apparent power analogue output functions
Function
Details
[Source] > Apparent power (S) > [Equipment] | L1 [kVA] The controller outputs the L1 apparent power.
[Source] > Apparent power (S) > [Equipment] | L2 [kVA] The controller outputs the L2 apparent power.
[Source] > Apparent power (S) > [Equipment] | L3 [kVA] The controller outputs the L3 apparent power.
[Source] > Apparent power (S) > [Equipment] | Total
[kVA]
The controller outputs the total apparent power.
[Source] > Apparent power (S) > [Equipment] | Min.
[kVA]
The controller outputs the apparent power of the phase with the lowest
apparent power.
[Source] > Apparent power (S) > [Equipment] | Max.
[kVA]
The controller outputs the apparent power of the phase with the highest
apparent power.
[Source] > Apparent power (S) > [Equipment] | Total [%]
The controller outputs the total apparent power, as a percentage of the
source's nominal apparent power.
[Source] > Apparent power (S) > [Equipment] | Available
[kVA]
The controller outputs the available apparent power for the source in
kVA. Available apparent power = Nominal apparent power - Total
apparent power
[Source] > Apparent power (S) > [Equipment] | Available
[%]
The controller outputs the available apparent power for the source, as a
percentage of the source's nominal apparent power. Available apparent
power = Nominal apparent power - Total apparent power
Table 3.14
[Source] power factor analogue output functions
Function
Details
[Source] > Power factor (PF) > [Equipment] | cos phi
The controller outputs the power factor, calculated as cos phi.
[Source] > Power factor (PF) > [Equipment] | Power factor
The controller outputs the power factor.