Selections for alarm inhibit:
Function
Description
Inhibit 1
Input function (alarm inhibit 1) or M-Logic output
Inhibit 2
M-Logic outputs: Conditions are programmed in M-Logic
Inhibit 3
GB ON
The generator breaker is closed
GB OFF
The generator breaker is open
Run status
Running detected and the timer in menu 6160 expired
Not run status
Running not detected or the timer in menu 6160 not expired
Generator voltage > 30 %
Generator voltage is above 30 % of nominal
Generator voltage < 30 %
Generator voltage is below 30 % of nominal
The timer in 6160 is not used if digital running feedback is used
Inhibit of the alarm is active as long as one of the selected inhibit functions is active.
In this example, inhibit is set to
Not run status
and
GB On
. Here, the alarm will be active when the generator
has started. When the generator has been synchronised to the busbar, the alarm will be disabled again
The inhibit LED on the base unit will activate when one of the inhibit functions is active.
Function inputs such as running feedback, remote start or access lock are never inhibited. On-
ly alarm inputs can be inhibited.