The setup of the multi-inputs and alarm parameters must be done in the above order. If not, the
alarm levels will be wrong.
Setting up decimals:
No decimals:
0 to 5 bar oil pressure transducer (4 to 20 mA)
Decimals = 0
Without use of decimals, the set point can only be adjusted in steps of one bar, which gives a very rough
range of setting.
The display will show 0 to 5 bar in the measuring range 4 to 20 mA.
One decimal:
0 to 5 bar oil pressure transducer (4 to 20 mA)
Decimals = 1
Auto scale = enable
Decimals = 1, AUTO SCALE = enabled