The load-dependent start relay reacts based on the power measurement of the controller together with the
breaker closed feedback.
Stop next generator (low load) (menu 6530)
The diagram shows that the stop relay activates after a delay. The timer starts when the load drops below the
adjusted stop level, and when the delay has expired, the relay activates.
The relay deactivates when the load exceeds the stop level when the off delay has expired. The off delay is
adjustable.
Power
Time
STOP LIMIT
Delay
Off delay
R
STOP
activates
R
STOP
deactivates
The load-dependent start relay reacts based on the power measurement of the controller together with the
breaker closed feedback.
Configuration
The settings are configured through the display or through the PC utility software.
PC utility software configuration
Configuration of “Start next gen”: