To avoid nuisance trips caused by reverse power, the synchronising settings can be set up
with a positive slip frequency.
LOAD
0% 100%
FUEL INDEX
0% 100%
FUEL INDEX
G1
G2
P
Gen1
P
Gen2
GB
GB
Illustration 1, POSITIVE slip frequency
______________________________________________________________________________________
LOAD
0% 100%
FUEL INDEX
0% 100%
FUEL INDEX
G1
G2
P
Gen1
P
Gen2
Reverse power
GB
GB
Illustration 2, NEGATIVE slip frequency
Adjustments
The dynamic synchroniser is selected in menu 2000 in the control setup and is adjusted in menu 2020 Sync.
Setting
Description
Comment
2021 f
MAX
Maximum slip frequency
Adjust the maximum positive slip frequency where synchro-
nising is allowed
2022 f
MIN
Minimum slip frequency
Adjust the maximum negative slip frequency where synchro-
nising is allowed
2023 U
MAX
Maximum voltage differrence
(+/- value)
The maximum allowed voltage difference between the bus-
bar/mains and the generator
2024 t
GB
Generator breaker closing
time
Adjust the response time of the generator breaker