RMI sensor
type
Temperature
Type 1
Type 2
Type 3
Type 4
°C
°F
Ω
Ω
Ω
Ω
40
104
291.5
480.7
69.3
Type 4 is not available when RMI
water is selected
50
122
197.3
323.6
60
140
134.0
222.5
36.0
70
158
97.1
157.1
80
176
70.1
113.2
19.8
90
194
51.2
83.2
100
212
38.5
62.4
11.7
110
230
29.1
47.6
120
248
22.4
36.8
7.4
130
266
28.9
140
284
22.8
150
302
18.2
The configurable type is configurable with eight points in the range 0 to 480 Ω. The tempera-
ture as well as the resistance can be adjusted.
If the RMI input is used as a level switch, then be aware that voltage must not be connected to
the input. If any voltage is applied to the RMI input, it will be damaged. Refer to the Application
Notes for further wiring information.
4.6.7 RMI fuel
This RMI input is used for the fuel level sensor.
RMI sensor type
Type 1
Value
Resistance
0 %
78.8 Ω
100 %
1.6 Ω
RMI sensor type
Type 2
Value
Resistance
0 %
3 Ω
100 %
180 Ω
If the RMI input is used as a level switch, then be aware that voltage must not be connected to
the input. If any voltage is applied to the RMI input, it will be damaged. Refer to the Application
Notes for further wiring information.
GPC-3 DRH 4189340587 UK