Recovery timer 2 (long interruption timer)
Menu 2291 = 3 s
Menu 2294 = 60 s
The long interruption timer will allow the MB to reconnect as soon as the mains voltage and frequency have
been uninterrupted within the timer setting in menu 2294 ("Recovery del. 2"). Then the MB can be closed.
The inhibit parameters for synchronising the MB are disabled by default.