TIME
Shows the alarm timer and the remaining time. The indicated remaining time is minimum remaining time. The
timer will count downwards when the set point has been exceeded.
Remaining time 1.0s
UP DOWN
G 0 0 0V
1010 G -P> 2
IN (digital input)
Shows the status of the digital inputs.
Input = 1
UP DOWN
G 0 0 0V
Digital input 108
OUT (digital output)
Shows the status of the digital outputs.
Output A 0
UP DOWN
G 0 0 0V
Relay 96
MISC
Shows the status of the M-Logic.
Various = 1
UP DOWN
G 0 0 0V
M-Logic enabled
The load-dependent start/stop functionality uses one relay for “start next generator” and one relay for “stop
next generator”. It is also possible just to use one of the functions if it is not desired to use both the start and
the stop function.
The function load-dependent start and stop does not give the possibilities of a power management system,
such as priority selection and available power calculations. This means that the switchboard manufacturer
must take care of starting and stopping the next genset(s) and their priority.
The relays can be used as inputs for the power management system as an example.
Start next generator (high load) (menu 6520)
The below diagram shows that the delay for the start relay starts when the load exceeds the adjusted start
limit. The relay will deactivate again when the load decreases below the start limit and the off delay has ex-
pired.