The unit offers the possibility of
Remote Start
mode of operation. Any digital input may be assigned as
Remote Start Input
using
Input Function Select
program parameters.
The
Remote Start
signal may be a NO or NC contact, switching to either battery positive or battery negative.
These selections are made using programming menu.
It is also necessary to set the
ACTION
program parameter of the related input to
3
in order to prevent any
alarm from this input.
When a
Remote Start
input is defined, the mains phases are not monitored. When the
Remote Start
signal is present then the mains will be supposed to fail, inversely when the
Remote Start
signal is
absent then mains voltages will be supposed to be present.
The front p
anels mimic diagram’s mains LEDs will always reflect the status of the
Remote Start
input.
The unit offers an optional
Disable Auto Start
signal input. Any digital input may be assigned as
Disable
Auto Start
using
Input Function Select
program parameters
.
It is also necessary to set the
ACTION
program parameter of the related input to
3
in order to prevent any
alarms generated from this input.
The
Disable Auto Start
signal may be a NO or NC contact, switching to either battery positive or battery
negative. These selections are made using the programming menu.
If the
Disable Auto Start
input is defined and the input signal is active, the mains phases are not
monitored and supposed to be inside limits. This will prevent the genset from starting even in case of a
mains failure. If the genset is running when the signal is applied, then usual Mains Waiting and Cooldown
cycles will be performed before engine stop. When the
Disable Auto Start
signal is present, the front
panels mimic
diagram’s mains LEDs will reflect the mains voltages as present.
When the signal is passive, the unit will revert to normal operation and monitor the mains voltage status.
The REMOTE START operation overrides DISABLE AUTO
START and FORCE TO START operations.
32.4. REMOTE START OPERATION
32.5. DISABLE AUTO START, SIMULATE MAINS
Содержание D-500
Страница 35: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 35 4 3 3 PHASE 3 WIRE DELTA 4 2 3 PHASE 4 WIRE STAR ...
Страница 38: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 38 4 9 1 PHASE 2 WIRE 4 8 2 PHASE 3 WIRE DELTA 2 CTs L1 L3 ...
Страница 43: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 43 6 2 AMF FUNCTIONALITY CTs AT ALTERNATOR SIDE ...
Страница 44: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 44 6 3 ATS FUNCTIONALITY ...
Страница 45: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 45 6 4 REMOTE START FUNCTIONALITY ...
Страница 46: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 46 6 5 ENGINE CONTROL FUNCTIONALITY ...
Страница 47: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 47 6 6 REMOTE DISPLAY PANEL FUNCTIONALITY ...
Страница 56: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 56 ...