The controller offers an automatic charge cycle for the engine battery.
When the engine battery weakens, the genset will run automatically during programmed period in an
unloaded state in order to charge the engine battery, protecting it from total discharge when the genset
has not run for a long time.
Related parameters:
Battery Charge Run Voltage:
If this parameter is different from zero and the engine battery voltage falls
below this limit then the controller will run the engine unloaded, in order to charge engine battery. The
running duration is determined by the
Battery Charge Run Timer
parameter.
Battery Charge Run Timer
: This parameter determines the engine battery charge running duration. The
minimum run time is 2 minutes.
Emergency Backup:
If this parameter if activated and the mains fails during engine battery charging run,
then the genset will take the load.
The controller offers 16 externally controllable digital output functions.
These output functions have no effect in the operation of the unit; however they can be redirected to any
digital output, allowing remote control of functions or external devices.
The remote control of these outputs are enabled through Modbus, Modbus TCP/IP and Rainbow Scada
remote control functions.
The outputs are in 16 bits of the same Modbus register, placed at address 11559d.
The controller offers a combat mode input function.
When a digital input is defined as Combat Mode and signal applied to this input, the controller will turn off
all led lamps and the backlight illumination 10 seconds after any key is pressed.
When a button is pressed, the illumination will be enabled for 10 seconds.
32.21. COMBAT MODE
Please review the Modbus manual for more details.
Output statuses are kept in a non-volatile memory and are not
affected by power failures.
32.20. EXTERNALLY CONTROLLED DIGITAL OUTPUTS
32.19. CHARGING THE ENGINE BATTERY
Содержание D-500
Страница 35: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 35 4 3 3 PHASE 3 WIRE DELTA 4 2 3 PHASE 4 WIRE STAR ...
Страница 38: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 38 4 9 1 PHASE 2 WIRE 4 8 2 PHASE 3 WIRE DELTA 2 CTs L1 L3 ...
Страница 43: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 43 6 2 AMF FUNCTIONALITY CTs AT ALTERNATOR SIDE ...
Страница 44: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 44 6 3 ATS FUNCTIONALITY ...
Страница 45: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 45 6 4 REMOTE START FUNCTIONALITY ...
Страница 46: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 46 6 5 ENGINE CONTROL FUNCTIONALITY ...
Страница 47: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 47 6 6 REMOTE DISPLAY PANEL FUNCTIONALITY ...
Страница 56: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 56 ...