D-500 User Manual Rev_06 Firmware V-5.8
K35D05-EN - 97 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
Service-2 Engine Hours
hours
0
5000
250
The
SERVICE REQUEST
led indicator
will turn on after this quantity of engine
hours from the last service. If the period
is set to ‘0’ no
SERVICE REQUEST
will
be generated depending on service-2
engine hours.
Service-2 Period
month
0
24
6
The
SERVICE REQUEST
led indicator
will turn on after this amount of time
from the last service. If the period is set
to ‘0’ no
SERVICE REQUEST
will be
indicated depending on Service-2
Period.
Service-2 Alarm Level
-
0
3
0
0:
no action
1:
shutdown alarm
2:
loaddump alarm
3:
warning
Service-3 Engine Hours
hours
0
5000
250
The
SERVICE REQUEST
led indicator
will turn on after this quantity of engine
hours from the last service. If the period
is set to ‘0’ no
SERVICE REQUEST
will
be generated depending on service-3
engine hours.
Service-3 Period
month
0
24
6
The
SERVICE REQUEST
led indicator
will turn on after this amount of time
from the last service. If the period is set
to ‘0’ no
SERVICE REQUEST
will be
indicated depending on Service-3
Period.
Service-3 Alarm Level
-
0
3
0
0:
no action
1:
shutdown alarm
2:
loaddump alarm
3:
warning
J1939 Enable
-
0
1
0
0: The J1939 port is inoperative.
1: The analog measurements (oil,
temp, and rpm) are picked up from
the ECU. If the ECU communication
is lost, then the engine will be
stopped.
J1939 Engine Brand
-
0
15
0
0: GENERIC
1: CUMMINS
2: DETROIT DIESEL
3: DEUTZ
4: JOHN DEERE
5: PERKINS
6: VOLVO
7: CATERPILLAR
8: SCANIA
9: IVECO
10: MTU-MDEC
11: BOSCH
Other values: Reserved. Do not use.
16.3. ENGINE PARAMETERS GROUP (continued)
Содержание D-500
Страница 35: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 35 4 3 3 PHASE 3 WIRE DELTA 4 2 3 PHASE 4 WIRE STAR ...
Страница 38: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 38 4 9 1 PHASE 2 WIRE 4 8 2 PHASE 3 WIRE DELTA 2 CTs L1 L3 ...
Страница 43: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 43 6 2 AMF FUNCTIONALITY CTs AT ALTERNATOR SIDE ...
Страница 44: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 44 6 3 ATS FUNCTIONALITY ...
Страница 45: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 45 6 4 REMOTE START FUNCTIONALITY ...
Страница 46: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 46 6 5 ENGINE CONTROL FUNCTIONALITY ...
Страница 47: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 47 6 6 REMOTE DISPLAY PANEL FUNCTIONALITY ...
Страница 56: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 56 ...