D-500 User Manual Rev_06 Firmware V-5.8
K35D05-EN - 100 -
These parameters allow adjusting the battery backup real time clock of the module. Once set, the clock
will continue to run even if DC power is removed from the unit.
Parameter Definition
Unit
Min
Max
Description
Date
-
01
31
Current day of the month.
Month
-
01
12
Current month.
Year
-
00
99
Last two digits of the current year.
Hours
-
00
23
Current hour of the day.
Minutes
-
00
59
Current minute of the hour.
Seconds
-
00
59
Current second of the minute.
In AUTO mode, it is possible to define the periods where automatic operation is desired. It may be
required that the genset does not start at night or weekends.
Weekly schedule programs allow an hourly setting of automatic operation of the unit during one week.
There are 7days x 24hours =144 parameters. Each hour of the week can be independently defined as
AUTO or OFF period.
If automatic operation is disabled by the weekly
exerciser, the AUTO led will flash.
16.5. WEEKLY OPERATION SCHEDULE
16.4. ADJUST DATE AND TIME
Содержание D-500
Страница 35: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 35 4 3 3 PHASE 3 WIRE DELTA 4 2 3 PHASE 4 WIRE STAR ...
Страница 38: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 38 4 9 1 PHASE 2 WIRE 4 8 2 PHASE 3 WIRE DELTA 2 CTs L1 L3 ...
Страница 43: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 43 6 2 AMF FUNCTIONALITY CTs AT ALTERNATOR SIDE ...
Страница 44: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 44 6 3 ATS FUNCTIONALITY ...
Страница 45: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 45 6 4 REMOTE START FUNCTIONALITY ...
Страница 46: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 46 6 5 ENGINE CONTROL FUNCTIONALITY ...
Страница 47: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 47 6 6 REMOTE DISPLAY PANEL FUNCTIONALITY ...
Страница 56: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 56 ...