D-500 User Manual Rev_06 Firmware V-5.8
K35D05-EN - 49 -
Term Function
Technical data
Description
13
DIGITAL INPUT 3
The input has programmable function.
Factory set as
EMERGENCY STOP
.
14
DIGITAL INPUT 4
The input has programmable function.
Factory set as
LOW COOLANT LEVEL
SWITCH
.
15
DIGITAL INPUT 5
The input has programmable function.
Factory set as
SPARE INPUT-1
.
16
DIGITAL INPUT 6
The input has programmable function.
Factory set as
SPARE INPUT-2
.
17
DIGITAL INPUT 7
The input has programmable function.
Factory set as
SPARE INPUT-3
.
18
DIGITAL INPUT 8
The input has programmable function.
Factory set as
FORCE OFF MODE
.
19
SENDER GROUND
Ground potential for analog senders.
Connect to the engine body, close to
senders.
20
ANALOG SENDER 1
(OIL PRESSURE SENDER)
Connect to the oil pressure sender.
Do not connect the sender to other
devices.
21
ANALOG SENDER 2
(COOLANT TEMP. SENDER)
Connect to the coolant temperature
sender. Do not connect the sender to
other devices.
22
ANALOG SENDER 3
(FUEL LEVEL SENDER)
Connect to the fuel level sender.
Do not connect the sender to other
devices.
23
ANALOG SENDER 4
(OIL TEMP SENDER)
Connect to the oil temperature sender.
Do not connect the sender to other
devices.
Term Function
Technical data
Description
24
PROTECTION GROUND
Output 0Vdc
Connect the protective shield of the RS-
485 cable to this terminal, from one end
only.
25
RS-485 B
Digital communication
port
Connect the A-B data lines of the RS-485
link to these terminals.
26
RS-485 A
27
MPU +
Analog input, 0.5 to
30V-AC
Connect the MPU unit to these inputs
Use a twisted cable pair or coaxial cable
for best results.
28
MPU -
29
PROTECTION GROUND
Output 0Vdc
Connect the protective shield of the MPU
and CANBUS-J1939 cables to this
terminal, from one end only.
30
CANBUS-H
Digital communication
port
Connect the J1939 port of an electronic
engine to these terminals.
The 120 ohm terminating resistors are
inside the unit. Please do not connect
external resistors.
Use a twisted cable pair or coaxial cable
for best results.
31
CANBUS-L
Содержание D-500
Страница 35: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 35 4 3 3 PHASE 3 WIRE DELTA 4 2 3 PHASE 4 WIRE STAR ...
Страница 38: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 38 4 9 1 PHASE 2 WIRE 4 8 2 PHASE 3 WIRE DELTA 2 CTs L1 L3 ...
Страница 43: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 43 6 2 AMF FUNCTIONALITY CTs AT ALTERNATOR SIDE ...
Страница 44: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 44 6 3 ATS FUNCTIONALITY ...
Страница 45: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 45 6 4 REMOTE START FUNCTIONALITY ...
Страница 46: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 46 6 5 ENGINE CONTROL FUNCTIONALITY ...
Страница 47: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 47 6 6 REMOTE DISPLAY PANEL FUNCTIONALITY ...
Страница 56: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 56 ...