D-500 User Manual Rev_06 Firmware V-5.8
K35D05-EN - 150 -
Modbus Slave Address:
may be set between 1 and 240. If only one unit is available in the same IP
address, it is advised to keep the default address (1).
Ethernet Enable:
This parameter should be set to 1 (or checked) in order to enable the ethernet port.
Modbus TCP/IP Port:
The usual setting is 502. However the unit is able to work on any port address.
User IP Mask:
There are 3 mask registers available. The use of the registers are emphasized in the D-
500/700 User Manual. Please set the first mask as 255.255.255.0 for the proper operation.
Ethernet Network IP:
May be left as 0.0.0.0 for automatic address claim or set to a value in order to
claim a defined address.
Ethernet Gateway IP:
Should be set in accordance with your local switch configuration.
Ethernet Subnet Mask:
Should be set in accordance with your local switch configuration.
The complete Ethernet port specifications are found in the
D-500/700 User Manual
.
Please rewiev the document
Ethernet Configuration Guide for D-500/700
for more details about the
ethernet port setup.
When a fault case occurs or the genset runs or the genset takes the load or the genset unloads or the
genset stops, an automatic SNMP TRAP message is send to the SNMP Client.
In order to enable SNMP TRAP messages, the Client has to send at least one SNMP request message to
the controller in order to inform it about its IP address. The controller records the address of the
last
SNMP Client and sends trap messages to this address.
The SNMP TRAP message message contains the controller operating mode, engine status and the alarm
list.
34.2. SNMP TRAP MESSAGES
34.1. PARAMETERS REQUIRED FOR SNMP VIA ETHERNET
Содержание D-500
Страница 35: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 35 4 3 3 PHASE 3 WIRE DELTA 4 2 3 PHASE 4 WIRE STAR ...
Страница 38: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 38 4 9 1 PHASE 2 WIRE 4 8 2 PHASE 3 WIRE DELTA 2 CTs L1 L3 ...
Страница 43: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 43 6 2 AMF FUNCTIONALITY CTs AT ALTERNATOR SIDE ...
Страница 44: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 44 6 3 ATS FUNCTIONALITY ...
Страница 45: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 45 6 4 REMOTE START FUNCTIONALITY ...
Страница 46: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 46 6 5 ENGINE CONTROL FUNCTIONALITY ...
Страница 47: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 47 6 6 REMOTE DISPLAY PANEL FUNCTIONALITY ...
Страница 56: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 56 ...