D-500 User Manual Rev_06 Firmware V-5.8
K35D05-EN - 84 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
Fuel Pulses per Volume
-
0
65000
1000
This is the number of pulses produced
by the flowmeter for the unit volume.
This parameter is characteristic of the
flowmeter used and should be set
according to the flowmeter data.
Fuel Counter Unit
Lt/gal
-
-
liters
This is the unit for the fuel counter
SMS on Engine
Run/Stop
-
0
1
0
This parameter controls SMS sending
when the engine runs or stops. No
warnings generated.
0:
no SMS on engine run/stop
1:
SMS sent on engine run/stop
E-mail on Engine
Run/Stop
-
0
1
0
This parameter controls e-mail sending
when the engine runs or stops. No
warnings generated.
0: no e-mail on engine run/stop
1: e-mail sent on engine run/stop
Trend Sample Interval
Sec
1
3600
1
WARNING: Available only in color
screen models.
This is the pixel period in trend
graphics. A short interval will slide the
graphic faster, while a long interval will
slow it down.
Fuel Counter Type
-
0
1
0
This parameter determines the purpose
of fuel pulses
0:
Fuel filling pulses, increment fuel
counter
1:
Fuel consumption pulses, display
consumption.
Dual Genset Equal Aging
Enabled
-
0
1
0
0:
Equal aging not enabled
1:
Equal aging enabled
CT Secondary Rating
-
0
1
0
0:
xxx/5A
1:
xxx/1A
Automatic Topology
Detection
-
0
1
0
If this parameter is enabled, when the
engine runs, the controller will detect
the connection topology automatically
and will select alarm levels accordingly.
0:
auto detect not enabled
1:
auto detect enabled
Maintenance Done
Warning Enable
-
0
1
0
If enabled, the unit will generate a non-
visual warning when maintenance
counters are reset. In consequence,
SMS and e-mails will be sent, the
warning will be visible on the central
monitoring system.
0:
maintenance warning disabled
1:
maintenance warning enabled
Stop Status Screens
-
0
1
0
0: Enable status screens
1: Disable status screens
Time Zone
min
-720
+720
0
This parameter adjusts the time zone of
the controller, in order to allow internal
real time clock to be synchronized to
the UTC time.
16.1. CONTROLLER CONFIGURATION GROUP (continued)
Содержание D-500
Страница 35: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 35 4 3 3 PHASE 3 WIRE DELTA 4 2 3 PHASE 4 WIRE STAR ...
Страница 38: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 38 4 9 1 PHASE 2 WIRE 4 8 2 PHASE 3 WIRE DELTA 2 CTs L1 L3 ...
Страница 43: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 43 6 2 AMF FUNCTIONALITY CTs AT ALTERNATOR SIDE ...
Страница 44: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 44 6 3 ATS FUNCTIONALITY ...
Страница 45: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 45 6 4 REMOTE START FUNCTIONALITY ...
Страница 46: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 46 6 5 ENGINE CONTROL FUNCTIONALITY ...
Страница 47: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 47 6 6 REMOTE DISPLAY PANEL FUNCTIONALITY ...
Страница 56: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 56 ...