D-500 User Manual Rev_06 Firmware V-5.8
K35D05-EN - 125 -
COMMAND
DESCRIPTION
ANSWER
GET IP
If GPRS connection is
active, the controller will
reply by an SMS message
indicating the IP address of
the GSM modem.
GPRS 1
Activates the GPRS
connection
GPRS 0
Stops the GPRS connection
RESET
ALARMS
Clears alarms of the controller.
The operating mode is not
modified.
REBOOT
Performs a hard reset on the
controller
no answer
MODEM RESET
Performs a hard reset on the
modem
no answer
GET INFO
Returns the alarm list and
actual measured values
ALARMS (if exists)
GEN: Vavg/ıAVG/kWtot/pf/Freq
MAINS:
Vavg/ıAVG/kWtot
OIL_PR/TEMP/FUEL%
SMS messages must be written exactly as below, without any preceding blanks.
Only
UPPERCASE
characters are permitted.
SMS messages are accepted only from phone numbers recorded in the
Communication>GSM>Message Numbers
tab.
Answers to SMS messages will be sent to
all
phone numbers in the list.
Alarms cleared!
GPRS disabled!
GPRS enabled!
IP: 188.41.10.244
29. SMS COMMANDS
Содержание D-500
Страница 35: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 35 4 3 3 PHASE 3 WIRE DELTA 4 2 3 PHASE 4 WIRE STAR ...
Страница 38: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 38 4 9 1 PHASE 2 WIRE 4 8 2 PHASE 3 WIRE DELTA 2 CTs L1 L3 ...
Страница 43: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 43 6 2 AMF FUNCTIONALITY CTs AT ALTERNATOR SIDE ...
Страница 44: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 44 6 3 ATS FUNCTIONALITY ...
Страница 45: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 45 6 4 REMOTE START FUNCTIONALITY ...
Страница 46: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 46 6 5 ENGINE CONTROL FUNCTIONALITY ...
Страница 47: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 47 6 6 REMOTE DISPLAY PANEL FUNCTIONALITY ...
Страница 56: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 56 ...