36 • dap4 User Manual
Available Selections:
Wtr Vlv (Water Valve): Engy Svg Cool
Chilled Wtr Cool
Chilled Wtr Reg
Aux Chill Wtr
None
Note:
If None is selected, Wtr Vlv Voltage, Wtr Vlv Action and Engy Lockout Time will appear on
the display module screen.
E-Saver Assist:
None
1 Comp*
2 Comp*
4 Comp*
* If E-Saver Assist is selected with 1, 2 or 4 compressors, the display module will display “Disch
Temp Is Required”. An optional discharge temperature sensor is required. If left at none, there
will be no message.
Note
: E-Saver Assist will only appear if either Engy Svg Cool or Aux Chill Wtr are selected.
Wtr Vlv Voltage:
0 – 10 (factory setting)
4
–
7
6
–
9
7
–
10
2
–
10
Wtr Vlv Action:
Direct (factory setting) or Reverse
Engy Lockout Time: 15m (factory setting), 30m, 45m, and 60m
Once a selection or selections have been made, move the cursor to the title block by pressing the
ENTER key
Press the DOWN key to view the next screen:
The following will be displayed (inputs are for reference only):
Available Selections:
Simple Setting:
0 – 300 (factory setting is 25)
Disch Air PID
Simple Settings:
25
Cntrol: PID
Band 5.8
o
F
Interaction Time:
234
Derivation Time:
23s
Output Period
0ms