42 • dap4 User Manual
The Set Point range is 45 to 60°F (factory setting is 52°F)
Once a selection or selections have been made, move the cursor to the title block by pressing the
ENTER key
▼ Press the DOWN key to view the next screen:
The following will be displayed (values are for reference only):
Available Selections:
Hi Humidity Alarm: Yes or No (factory setting is Yes)
Set Point:
The range is 35 to 90% RH (factory setting is 60% RH)
Lo Humidity Alarm: Yes or No (factory setting is Yes)
Set Point:
The range is 10 to 65% RH (factory setting is 40% RH)
Note:
If No is selected for the Hi or Lo Humidity Alarm, the Set Point will not be displayed.
Once a selection or selections have been made, move the cursor to the title block by pressing the
ENTER key
▼ Press the DOWN key to view the next screen:
The following will be displayed (values are for reference only):
Discharge Alarm
Lo Disch T Alarm:
Yes
Set Point:
52
o
F
Humidity Alarms
Hi Humidity Alarm:
Yes
Set Point:
60%
Lo Humidity Alarm:
Yes
Set Point:
40%