26 • dap4 User Manual
MENU G – NETWORK CONFIG
MENU G allows selection of BMS protocol. (Service Level password is required for entry)
Once password has been entered, press the UP or DOWN key until “G. Network Config” appears
and is highlighted. Press the ENTER key.
The following will be displayed (values are for reference only):
Only the protocol can be changed. The selections are as follows:
LON, BACNET, PCOLOAD, MODBUS, MODEM, CAREL, N/A
Once the selection has been made, press the ENTER key and the cursor will move to the title
block.
To move to the next screen, press the DOWN key.
The following will be displayed (values are for reference only):
The address can be a value from 0 to 999
The available baud rates are: 1200, 2400, 4800, 9600, 19200
Once the selection has been made, press the ENTER key to move the cursor to the title block.
▼ Press the Esc key to return to the Main Menu. Scroll to the next menu to be viewed is high-
lighted or press the Esc again to return to the normal operating mode.
Bms Configuration
BMS Port 1
Protocol: MODBUS
Bms Configuration
BMS Port 1
Address 1
Baud Rate
19200