61 • dap4 User Manual
With Enable OFF
With Enable ON
The “Choose Name” allows one of the following to be selected by moving the cursor to the
Choose Name and pressing the UP or DOWN key:
Diff Pressure Suct Pressure Disch Pressure Outside Hum Outside Temp Zone Humidity
Zone Air Temp CW Flow
Cond Wtr Flow Ret Air Temp Sply Air Temp CW Ret Temp
CW Sply Temp Cond Ret Temp Cond Sup Temp Power
Frequency
Ground Amps
Neutral Amps Output Amps C Output Amps B Output Amps A Input Amps C Input Amps B
Input Amps A Output V. B-C Output V. A-C
Output V. A-B Input V. B-C
Input V. A-C
Input V. A-B
Once a selection or selections have been made, move the cursor to the title block by pressing the
ENTER key
▼ Press the DOWN key to view the next screen:
The following will be displayed (values are for reference only):
Move the cursor by pressing the ENTER key. Move the cursor to change the setting.
The following can be changed by pressing the DOWN key:
Channel – there are six (6) selections (Y1, Y2, Y3, Y4, Y5 and Y6). There are five Analog
outputs available. DO NOT ASSIGN THE SAME CHANNEL ON MORE THAN ONE ANA-
LOG OUTPUT.
Action: there are two choices; DIRECT AND REVERSE
Minimum: the range is from 0.0vdc to 10.0vdc
Maximum: the range is from 0.0vdc to 10.0vdc
Optional Sensor #4
Enable: OFF
Choose Name
Normal NTC
Offset 0.0
o
F
Value: -2.1
o
F
Analog Output Config
Channel: Y6
Action: DIRECT
Minimum 0.0vdc
Maximum: 0.0vdc
Содержание dap4 touch
Страница 4: ......
Страница 101: ...101 dap4 User Manual...
Страница 111: ...111 dap4 User Manual...