37 • dap4 User Manual
Control: PID
P + 1
P
Notes:
If selecting PID, the Band, Integration Time, Derivative Time and Output Period will appear on the
screen and values can be entered.
If selecting P + 1, the Band, Integration Time and Output Period will appear on the screen and
values can be entered.
If selecting P, the Band and Output Period will appear on the screen and values can be entered.
Band:
The range is 1 to 35°F
Integration Time: The range is 0 to 999 seconds
Derivative Time:
The range is 0 to 999 seconds
Output Period:
The range is 0 to 9999 ms (milliseconds)
Once a selection or selections have been made, move the cursor to the title block by pressing the
ENTER key or press the Esc key to return normal operating mode
Press the DOWN key to view the next screen:
The following will be displayed (inputs are for reference only):
Available Selections:
Humidify:
Compu Non-Mod (Computer Room, Non-Modulating)
Computer Mod (Computer Room, Modulating)
Comf Non-Mod (Comfort, Non-Modulating)
Consult with factory
Comf Mod (Comfort, Modulating)
Consult with factory
None
Auto-Flush:
Not Used or 12, 24, 48 or 96 Hrs
(only available on units with infrared humidifier)
Dsat Cyc:
Not Used or 1, 2, 3, 4 or 5 M Off (Minutes)
Hum Anticipation: On or Off
Humidity Settings
Control:
Dew Point
Humidify:
Compu Non-Mod
Auto-Flush: 24Hrs
Dsat Cyc:
Not Used
Hum Anticipation:
Off
Dehum Mode:
1C In Limit